SensoIRIS MCP150PR

The addressable manual call point SensoIRIS MCP150PR is designed for application in addressable fire alarm systems, which support TTE communication protocol. The call point has a built-in isolator module which when used allows continuous operation of the loop in case of short circuit and without need of using additional isolator modules. The call point is powered on from the fire panel and can be controlled via the communication protocol.

 

SensoIRIS MCP150PR is certified according to standards EN54-11 and EN54-17!

 

Functional features
  • Working element (2 parts):
    •  Frangible element - non-resettable (a break glass);
    • Operating element - resettable (a button)
  • Call point type (method of operation according EN 54-11) - B;
  • Built-in isolator module;
  • EN54-11 and EN54-17 certified.
Click on the image for larger view
Operating voltage 15÷32VDC
Current consumption without communication (max) 125µА@27VDC
Current consumption with communication (max) 160µА@27VDC
Current consumption in Fire mode 3mA
Wiring cables 0.5mm² ÷2.5mm²
Working temperature -10°C ÷ +60°C
Material, color ABS, red
Indication “Fire alarm” red LED
Dimensions 125x125x36mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical Documentation
SensoIRIS MCP150PR/PB - Instalation Manual
Updated on2019.03.06
Size0.64 MB
Download
Certificates
SensoIRIS MCP150PR - EN54 Certificate
Updated on2019.03.06
Size1.70 MB
Download